Procedure for IC693ALG390 Field Calibration What you will need: ❍ Calibrated DVM capable of displaying 10VDC +/- 0.1mV. ❍ IBM PC / Compatible running LM90 or a HHP. ❍ Resistor - 2K ohm @ 1% tolerance, Capacitor - 2000pF ❍ Non-Conductive Potentiometer adjuster. ● 1. Power off the 9030 PLC that has the analog card that is in need of calibration. 2. Remove any field wiring. 3. Wire the Resistor and Capacitor across terminals 3 and 5 as shown. 4. Wire the Voltage input and Common leads on the DVM to terminals 3 and 5 on the Analog Card respectively